Motors & Loads calculator
Motor Current Calculator
Use this page for the formula and nameplate side of motor-current work: estimate running current from horsepower or kW, voltage, efficiency, and power factor, then compare that value with the NEC table FLC when a table value is available. A 10 HP, 460V, three-phase motor at 90% efficiency and 0.85 power factor calculates to about 12.2 A by formula, while NEC Table 430.250 lists 14 A. If the job is only an NEC 430.250 lookup such as 10 HP or 200 HP at 460V, use the full-load-current calculator. If the job is inrush or locked-rotor screening, use the motor-starting-current calculator. This page stays useful as the comparison and planning bridge between those steps.
Updated June 21, 2026
A 10 HP, 460V, 3-phase motor at 90% efficiency and 0.85 power factor calculates to about 12.2A by formula, while NEC Table 430.250 lists 14A for table FLC.
Formula current explains the operating point | Table FLC still drives branch-circuit sizing and nameplate FLA still drives overload settings
Enter motor power, voltage, efficiency, and power factor below to compare formula running current with NEC table FLC and choose the correct next workflow
Calculator Inputs
Calculation Results
Enter values above to see calculation results
Field kit
Tools for motor current checks
Compare the estimated current with measured values and control parts that match the motor nameplate.
As an Amazon Associate I earn from qualifying purchases.
Calculation history
Example Calculations
10 HP, 460V, three-phase AC motor
The NEC table value is 14 A. A branch-circuit conductor screen at 125% gives 17.5 A. If the actual nameplate FLA is 12.8 A and the service factor allows 125%, the overload-device screen is 16.0 A.
- Calculation Mode: Conductor sizing
- Motor Power: 10
- Power Unit: Hp
- Voltage: 460
- Phases: Three phase
- Service Factor: 1.15
- Nameplate FLA: 12.8
50 HP, 460V, DOL starting screen
The NEC table value is 65 A. Using the DOL screening multiplier of 6 x FLC gives about 390 A of starting current for planning-level feeder review.
- Calculation Mode: Starting Current
- Motor Power: 50
- Power Unit: Hp
- Voltage: 460
- Phases: Three phase
- Starting Method: Direct online
How to Use
Motor Current Calculator for Formula Amps, Nameplate Checks, and NEC Next Steps
Use this page when you need to estimate or compare motor current from the motor's operating data: horsepower or kW, voltage, efficiency, and power factor. For example, a 10 HP, 460V, three-phase motor at 90% efficiency and 0.85 power factor calculates to about 12.2 A by formula, while the NEC 430.250 table value for the same HP and voltage is 14 A. That comparison is useful because formula current, NEC table FLC, nameplate FLA, starting current, and protection settings do not all serve the same job.
What Each Mode Does
- NEC Table FLC vs Formula Current - compares entered motor data with the NEC table full-load current for the selected horsepower, voltage, and phase count.
- Starting Current Screen - provides only a light bridge to inrush planning. Use the dedicated Motor Starting Current Calculator when the task is really locked-rotor current, inrush, DOL, star-delta, soft starter, VFD, or autotransformer comparison.
- Operating Current - estimates running current, kW, kVAR, and kVA from the entered power, efficiency, and power factor.
- Preliminary Branch-Circuit Sizing - shows why branch work starts from NEC table FLC, then points deeper conductor and protection tasks toward the dedicated FLC, cable-sizing, and protection calculators.
FLC vs FLA: The NEC Distinction That Drives the Whole Page
NEC 430.6(A)(1) sends branch-circuit conductor sizing and branch-circuit short-circuit and ground-fault protection back to the standard ampere ratings in the NEC motor tables. For the AC motors covered by this page, that means Table 430.248 for single-phase motors and Table 430.250 for three-phase motors.
NEC 430.22 then uses that table full-load current for conductor ampacity. NEC 430.32 is different: overload devices are based on actual motor nameplate current, not the NEC table value. That is why this calculator does not pretend that one current value does every job.
| Current Basis | Source | Typical Use |
|---|---|---|
| Table FLC | NEC 430.248 or 430.250 | Conductor sizing and inverse-time breaker screening under NEC Article 430 |
| Nameplate FLA | Motor nameplate | Overload-device settings under NEC 430.32 |
| Formula Current | Power, voltage, efficiency, and power factor | Comparison, operating-current review, and general load screening |
Three-Phase NEC Table 430.250 Quick Reference
The following values are common checkpoints for three-phase AC motors. They are useful when you want to sanity-check the calculator output or compare nearby horsepower values before moving to conductor and breaker review.
| Motor Size | 230V | 460V | 575V |
|---|---|---|---|
| 10 HP | 28 A | 14 A | 11 A |
| 25 HP | 68 A | 34 A | 27 A |
| 50 HP | 130 A | 65 A | 52 A |
| 100 HP | 248 A | 124 A | 99 A |
How the Branch-Circuit Sizing Screen Is Framed
The branch-circuit sizing mode is intentionally narrow. It uses 125% of NEC table FLC for a conductor ampacity screen under NEC 430.22 and applies a 250% inverse-time circuit-breaker screen under NEC 430.52 and NEC 240.6(A) standard sizes. For overload devices, the page only calculates a setting if you enter actual nameplate FLA, because that is what NEC 430.32 uses.
Starting Current Mode Is a Screening Tool, Not a Locked-Rotor Study
The starting-current mode uses common planning multipliers for DOL, star-delta, soft starter, VFD, and autotransformer starts. That is helpful for quick feeder and nuisance-trip discussions, but it is not a replacement for locked-rotor current data, commissioned soft-starter current limits, VFD overload settings, or a manufacturer starting study. For deeper inrush work, use the dedicated Motor Starting Current Calculator.
When to Use the Dedicated Full Load Current Tool Instead
If your job is only to look up NEC table current and branch-circuit sizing from horsepower, voltage, and phase count, use the Full Load Current Calculator. That page is the direct lookup page for examples such as NEC Table 430.250 10 HP 460V FLC and 200 HP 460V FLC. When the next question is motor branch short-circuit and ground-fault protection, move from the FLC result to the Motor Branch Protection Calculator, not to the general breaker page first. This page keeps formula current, operating-current review, and the next-step links together for one-motor planning.
Worksheet Follow-Ups After the Current Result
Use this current page for formula amps, table FLC comparison, and nameplate FLA context. Use the Motor Nameplate Data Worksheet when the next step is recording nameplate FLA, service factor, duty, and manufacturer notes. Use the Motor Contactor Selection Worksheet when coil voltage, NEMA basis, auxiliary contacts, enclosure, and SCCR notes need to stay with the starter selection.
What the Page Does Not Claim
This calculator does not claim to size every motor circuit in every condition. It does not handle every specialty motor type, every reduced-voltage starter detail, every conductor derating case, or every branch-circuit protection device option. Use it as an honest AC motor planning page, then verify the final design with the adopted NEC edition, actual nameplate data, and manufacturer documentation.
Common Applications
Comparing formula current with NEC table FLC for one AC motor
Checking whether entered efficiency and power factor explain a measured running current
Routing pure NEC table lookup work to the full-load-current page
Routing inrush and locked-rotor work to the dedicated starting-current page
One-motor load checks for panel, feeder, and transformer planning
Separating table FLC duties from nameplate FLA duties
Fast reference for common 230V, 460V, and 575V AC motor checkpoints
Frequently Asked Questions
Why does the calculator show both NEC table FLC and formula current?
Why do overload devices need nameplate FLA instead of NEC table FLC?
Does the branch-circuit sizing mode replace a full conductor-sizing review?
Can I use the starting-current mode as a true locked-rotor current value?
What is the fastest way to screen a standard 10 HP, 460V, three-phase motor?
Related Calculators
Full Load Current Calculator
Owns NEC Table 430.248/430.250 FLC lookup by HP, voltage, and phase, including 10 HP and 200 HP at 460V field checks.
ExploreMotor Starting Current Calculator
Compare induction-motor DOL, star-delta, soft-starter, VFD, and autotransformer starting current screens.
ExploreMotor Cable Size Calculator
Screen NEC table motor conductor size with ampacity derating, termination limits, and branch-circuit voltage drop.
ExploreMotor Power
Open the motor power for related motors & loads review.
ExploreCircuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
ExploreWire Size Calculator
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
Explore