intermediateFeatured

Voltage Drop Formulas & Calculation Reference

Single-phase and three-phase voltage-drop checks for feeders and branch circuits using run length, conductor resistance, and load current.

16 min read
Updated 2/2/2026
EleCalculator Team

Quick Answer: Single-phase: VD = 2×K×I×D / CM | Three-phase: VD = 1.732×K×I×D / CM (K = 12.9 Cu, 21.2 Al; D = one-way distance in ft; CM = circular mils). NEC targets: branch circuit ≤3%, feeder ≤3%, total ≤5% (Informational Notes — NEC 210.19/215.2). Example: 20A on 12 AWG Cu (CM=6,530), 75ft → VD = (2×12.9×20×75)/6,530 = 5.93V = 4.9% — over limit; upsize to 10 AWG (CM=10,380) → 3.1% ✓. → Voltage Drop Calculator

Quick Formula Reference

Circuit Type CM Formula Resistance Formula
Single-Phase VD = 2×K×I×D / CM VD = 2×I×R×L
Three-Phase VD = 1.732×K×I×D / CM VD = 1.732×I×R×L
Solve for CM CM = 2×K×I×D / VD_max CM = 1.732×K×I×D / VD_max

Where K = 12.9 (copper at 75°C), 21.2 (aluminum at 75°C); D = one-way conductor length (ft); CM = conductor area in circular mils.


NEC Voltage Drop Guidelines

Recommended Maximum Voltage Drop

Application Branch Circuit Feeder Total (Feeder + Branch)
NEC Recommendation 3% max 3% max 5% max
Sensitive Equipment 2% max 2% max 3% max
Motor Circuits 3% max 3% max 5% max

Note: NEC 210.19(A) and 215.2(A) Informational Notes recommend these limits for "reasonable efficiency of operation."

Voltage at Load

V_load = V_source - V_drop

Example: 120V source, 3% drop

V_drop = 120V × 0.03 = 3.6V
V_load = 120V - 3.6V = 116.4V

Single-Phase Voltage Drop Formulas

Standard Formula

V_drop = 2 × I × R × L

Where:

  • V_drop = Voltage drop (Volts)
  • I = Current (Amperes)
  • R = Resistance per unit length (Ohms/foot or Ohms/meter)
  • L = One-way length of conductor (feet or meters)
  • 2 = Factor for round-trip (supply and return)

Using Circular Mils

V_drop = (2 × K × I × D) / CM

Where:

  • K = Resistivity constant (12.9 for copper, 21.2 for aluminum)
  • I = Current (Amperes)
  • D = One-way distance (feet)
  • CM = Wire area in circular mils

Percentage Voltage Drop

V_drop (%) = (V_drop / V_source) × 100

Three-Phase Voltage Drop Formulas

Standard Formula

V_drop = √3 × I × R × L

Or equivalently:

V_drop = 1.732 × I × R × L

Using Circular Mils

V_drop = (1.732 × K × I × D) / CM

Three-Phase Percentage

V_drop (%) = (V_drop / V_L-L) × 100

Wire Resistance Reference

Copper Wire Resistance (Ohms per 1000 feet)

AWG DC Resistance AWG DC Resistance
14 3.14 Ω 2 0.194 Ω
12 1.98 Ω 1 0.154 Ω
10 1.24 Ω 1/0 0.122 Ω
8 0.778 Ω 2/0 0.0967 Ω
6 0.491 Ω 3/0 0.0766 Ω
4 0.308 Ω 4/0 0.0608 Ω
3 0.245 Ω 250 kcmil 0.0515 Ω

Circular Mil Areas

AWG Circular Mils AWG Circular Mils
14 4,110 2 66,360
12 6,530 1 83,690
10 10,380 1/0 105,600
8 16,510 2/0 133,100
6 26,240 3/0 167,800
4 41,740 4/0 211,600

Quick Reference: Maximum Distance Tables

Single-Phase 120V (3% Drop, Copper)

Load (A) 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG
10 45 ft 70 ft 115 ft 180 ft 290 ft
15 30 ft 45 ft 75 ft 120 ft 190 ft
20 22 ft 35 ft 55 ft 90 ft 145 ft
25 28 ft 45 ft 70 ft 115 ft
30 38 ft 60 ft 95 ft

Single-Phase 240V (3% Drop, Copper)

Load (A) 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG
10 90 ft 140 ft 230 ft 360 ft 580 ft
15 60 ft 90 ft 150 ft 240 ft 385 ft
20 45 ft 70 ft 115 ft 180 ft 290 ft
30 75 ft 120 ft 190 ft
40 90 ft 145 ft

Three-Phase 480V (3% Drop, Copper)

Load (A) 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG
20 175 ft 280 ft 440 ft 700 ft 1,115 ft
30 115 ft 185 ft 295 ft 465 ft 745 ft
50 70 ft 110 ft 175 ft 280 ft 445 ft
75 75 ft 120 ft 185 ft 295 ft
100 90 ft 140 ft 225 ft

Worked Examples

Example 1: Single-Phase Residential

Given: 20A load, 120V, 75 feet one-way, copper wire

Find: Required wire size for 3% max drop

Solution:

  1. Calculate allowable voltage drop:
V_drop (max) = 120V × 0.03 = 3.6V
  1. Using the CM formula, solve for CM:
CM = (2 × K × I × D) / V_drop
CM = (2 × 12.9 × 20A × 75ft) / 3.6V
CM = 38,700 / 3.6 = 10,750 CM
  1. Select wire: 10,750 CM → 10 AWG (10,380 CM is close, use next size up)

Verify:

V_drop = (2 × 12.9 × 20 × 75) / 10,380 = 3.73V (3.1%)

Answer: Use 10 AWG copper (or 8 AWG for margin)

Example 2: Three-Phase Industrial

Given: 100A load, 480V, 200 feet, copper, PF = 0.85

Find: Wire size for 3% max drop

Solution:

  1. Allowable drop:
V_drop (max) = 480V × 0.03 = 14.4V
  1. Using resistance method:
V_drop = √3 × I × R × L
14.4V = 1.732 × 100A × R × 200ft
R = 14.4 / (1.732 × 100 × 0.2) = 0.416 Ω/1000ft
  1. From resistance table: 2 AWG = 0.194 Ω/1000ft ✓

Verify:

V_drop = 1.732 × 100A × 0.000194 × 200 = 6.7V (1.4%)

Answer: Use 2 AWG copper

Example 3: Long Distance Motor Feeder

Given: 50 HP motor, 480V 3-phase, 500 feet, PF = 0.87

Find: Wire size for 3% drop

Solution:

  1. Calculate motor FLC (from NEC table): 65A

  2. Allowable drop: 480V × 0.03 = 14.4V

  3. Required CM:

CM = (1.732 × K × I × D) / V_drop
CM = (1.732 × 12.9 × 65A × 500ft) / 14.4V
CM = 726,063 / 14.4 = 50,421 CM
  1. Select: 1 AWG (83,690 CM) or 1/0 AWG (105,600 CM)

Answer: Use 1 AWG minimum, recommend 1/0 AWG for motor starting


Factors Affecting Voltage Drop

Temperature Correction

Wire resistance increases with temperature:

R_T = R_25 × [1 + α × (T - 25)]

Where:

  • R_25 = Resistance at 25°C
  • α = Temperature coefficient (0.00393 for copper)
  • T = Operating temperature (°C)

Power Factor Effect

For AC circuits with significant reactance:

V_drop = I × L × (R × cos(θ) + X × sin(θ))

Where X = reactance (significant for larger conductors)

Conductor Material

Material K Factor Relative Resistance
Copper 12.9 1.00 (baseline)
Aluminum 21.2 1.64× copper

Voltage Drop vs Wire Size Trade-offs

Cost-Benefit Analysis

Factor Smaller Wire Larger Wire
Initial cost Lower Higher
Voltage drop Higher Lower
Energy loss Higher Lower
Heat generation More Less
Future capacity Limited Available

When to Exceed Minimum

Consider upsizing wire when:

  • Long distance runs
  • Motor circuits (starting voltage)
  • Sensitive electronic equipment
  • Expected load growth
  • High duty cycle operations

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Using one-way distance for single-phase Misses return conductor Use 2×L factor
Ignoring 3-phase √3 factor Result off by 15% Use 1.732 factor
Using DC resistance for large AC conductors Ignores skin effect Use AC resistance tables
Forgetting to check both ampacity AND drop May still be undersized Verify both requirements

Related Calculators

Calculator Use When...
Voltage Drop Calculator Quick sizing calculations
Wire Size Calculator Complete wire selection
Conduit Fill Calculator Selecting conduit size
Motor Circuit Calculator Motor feeder sizing

Summary

Key Formulas:

  • Single-Phase: V_drop = 2 × I × R × L
  • Three-Phase: V_drop = √3 × I × R × L
  • CM Method: V_drop = (2 × K × I × D) / CM

NEC Recommendations:

  • Branch circuit: 3% max
  • Feeder: 3% max
  • Total: 5% max

K Factors:

  • Copper: 12.9
  • Aluminum: 21.2

FAQ

What is acceptable voltage drop per NEC?

NEC recommends (but doesn't require) maximum 3% drop for branch circuits and feeders, with 5% total from source to load. These are informational notes, not mandatory requirements.

Why does voltage drop matter?

Excessive voltage drop causes: reduced equipment performance, motor overheating, dimming lights, tripped breakers, and wasted energy as heat in conductors.

How do I reduce voltage drop?

Options include: using larger wire, shortening the distance, increasing voltage (208V vs 120V), using higher power factor, or running multiple parallel conductors.

Do I need to consider voltage drop for short runs?

For runs under 50 feet, voltage drop is usually not a concern for typical residential loads. Always verify for high-current circuits regardless of distance.

Should I use copper or aluminum for long runs?

Copper has lower resistance but costs more. For long runs, the cost difference may favor aluminum with larger gauge. Consider: initial cost, installation labor, terminal compatibility, and conduit fill.

Tags

voltage dropwire sizingNECformulas

Related Calculators

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.