Wire & Cable calculator
Wire Ampacity Calculator
This ampacity calculator starts with the field checks many users need: 12 AWG copper THHN can begin at a 30A 90°C insulation value for derating, but a 60°C equipment termination caps the final result at 20A. A common derating case, 10 AWG copper THHN at 45°C with nine current-carrying conductors, screens at about 24.4A before the 75°C terminal cap. Use this page for individual insulated conductors checked by table ampacity, ambient-temperature correction, conductor-count adjustment, and 60°C or 75°C termination limits. Use the conduit-fill page separately when the question is how many conductors physically fit in the raceway.
Updated June 14, 2026
12 AWG copper is commonly checked at 20A on a 60°C terminal basis or 25A on a 75°C basis, even though 90°C insulation can start higher for derating.
10 AWG Cu THHN at 45°C with 9 conductors -> 40A × 0.87 × 0.70 = 24.4A before the 75°C terminal cap
Choose conductor size, insulation, temperature, conductor count, and termination rating below to calculate final ampacity
Calculator Inputs
Calculation Results
Enter values above to see calculation results
Field kit
Tools for conductor work
Keep the calculated ampacity separate from installation approval, then choose basic tools for prep and current checks.
As an Amazon Associate I earn from qualifying purchases.
Calculation history
Example Calculations
12 AWG copper branch-circuit check
12 AWG copper THHN at 30°C with three current-carrying conductors and a 60°C termination basis.
- Wire Gauge: 12
- Wire Type: Copper
- Insulation Type: THHN/THWN-2
- Ambient Temperature: 30
- Current-Carrying Conductors: 3
- Termination Rating: 60
10 AWG copper with nine current-carrying conductors
10 AWG copper THHN at 45°C with nine current-carrying conductors and a 75°C termination basis.
- Wire Gauge: 10
- Wire Type: Copper
- Insulation Type: THHN/THWN-2
- Ambient Temperature: 45
- Current-Carrying Conductors: 9
- Termination Rating: 75
How to Use
How to use the ampacity calculator
- Select the wire gauge and conductor material that match the installation.
- Choose the insulation family. THW/THWN uses the 75°C column; THHN/THWN-2 and XHHW/XHHW-2 use the 90°C column as the starting point.
- Enter the ambient temperature and the number of current-carrying conductors.
- Select the governing equipment termination rating. The calculator uses that column as the final cap after derating.
- Review the adjusted ampacity, the termination limit, and the final ampacity.
What each result means
- Base Ampacity is the table ampacity before any adjustments.
- Combined Derating Factor multiplies the temperature factor by the current-carrying-conductor adjustment factor.
- Adjusted Ampacity applies the ambient-temperature and conductor-count factors.
- Termination Limit is the ampacity permitted by the selected 60°C or 75°C terminal column.
- Final Ampacity is the lower of the adjusted ampacity and the selected termination limit.
- Limiting Factor shows whether derating or the selected termination column controls the result.
- Continuous Load Planning Check shows the current level that corresponds to a 125% conductor-sizing check.
Common reference values
| Conductor | 60°C | 75°C | 90°C |
|---|---|---|---|
| 12 AWG copper | 20A | 25A | 30A |
| 10 AWG copper | 30A | 35A | 40A |
| 12 AWG aluminum | 15A | 20A | 25A |
| 2/0 aluminum | 115A | 135A | 150A |
This calculator is intentionally limited to the table-ampacity workflow for individual insulated conductors. It does not model free-air ampacity, cable-tray rules, rooftop temperature adders, direct burial, or voltage drop. Use the related tools below when your project needs those checks.
For a full conductor-selection workflow, combine this page with the Wire Size Calculator, the Voltage Drop Calculator, and the Conduit Fill Calculator. Move to the Breaker Sizing Calculator only after the load current and final conductor ampacity basis are known, because breaker review also depends on load type and small-conductor limits. For a longer explanation of conductor-count adjustment and temperature correction, see the Ampacity and Derating Guide.
Common Applications
Checking branch-circuit conductors against a 60°C terminal basis
Reviewing feeder conductors with a 75°C terminal basis
Evaluating conductor ampacity in hot mechanical rooms or attics
Comparing copper and aluminum conductor options for the same load
Reviewing multi-circuit raceways before final wire-size selection
Frequently Asked Questions
Why is the final ampacity sometimes lower than the adjusted ampacity?
When should I choose 60°C instead of 75°C terminations?
Does the neutral count as a current-carrying conductor?
Does this calculator cover free-air or cable-tray ampacity?
Related Calculators
Wire Size Calculator
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
ExploreVoltage Drop Calculator
Calculate voltage drop in conductors
ExploreConduit Fill Calculator
Check conduit fill, conductor count, and raceway loading against NEC-style limits.
ExploreCable Tray Fill Calculator
Preliminary tray-occupancy screen for tray area, cable area, and remaining space.
ExploreCable Ampacity Calculator
Use for cable assemblies such as NM-B, MC, and AC/BX where the jacketed cable rules differ from individual conductors in raceway.
ExploreCircuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
Explore