Wire & Cable calculator
Cable Ampacity Calculator
Multi-conductor cable ampacity calculator implementing NEC 2023 standards for assembled cables with multiple insulated conductors in a single jacket. Essential for Type NM-B (Romex), Type MC (Metal-Clad), Type AC (Armored Cable/BX) installations per code requirements.
Updated June 8, 2026
Example Calculations
Residential Kitchen: 12/2 NM-B Cable
12/2 NM-B (Romex) for 20A kitchen receptacle circuit. NEC 334.80 limits NM-B to 60°C rating (20A for 12 AWG). 12 AWG copper at 60°C = 20A max per NEC Table 310.16.
- Cable Type: 12/2 NM B
- Conductor Size: 12 AWG Copper
- Temperature: 30°C (86°F)
- Installation: Through Wall Cavities
Commercial Building: 10/3 MC-THHN
10/3 Type MC cable with THHN conductors for commercial feeder. 90°C rating allows 40A starting point, but use 75°C termination limit (35A) per NEC 110.14(C).
- Cable Type: 10/3 MC THHN
- Conductor Size: 10 AWG Copper
- Temperature: 30°C Ambient
- Installation: Exposed In Cable Tray
How to Use
NEC Multi-Conductor Cable Ampacity Standards
Cable vs Conductor: Multi-conductor cables contain 2+ insulated conductors in a single jacket/armor. Ampacity differs from individual conductors due to thermal characteristics and NEC application rules.
Cable Type Comparison: NM-B vs MC vs AC (Critical Selection Guide)
| Feature | Type NM-B (Romex) | Type MC (Metal-Clad) | Type AC (BX) |
|---|---|---|---|
| Temperature Rating | 60°C only (NEC 334.80) | 90°C (THHN/XHHW) | 60°C typical |
| Max Ampacity | 60A limit (NEC 334.80) | No limit (use Table 310.16) | Typically ≤30A branch circuits |
| Permitted Locations | Residential, ≤3 story buildings | All occupancies, exposed OK | Residential, concealed locations |
| Commercial Use | Prohibited >3 floors (334.10) | Permitted (NEC 330.10) | Limited - prefer MC |
| Mechanical Protection | PVC jacket only | Aluminum/steel armor | Galvanized steel armor |
| Typical Cost (12/2) | $0.40-0.60/ft | $1.20-1.80/ft | $0.90-1.20/ft |
| Best For | Residential branch circuits | Commercial, high-ampacity feeders | Residential retrofit (old work) |
Selection Rule: Use NM-B for residential ≤60A. Use Type MC for: (1) Commercial buildings, (2) Ampacity >60A, (3) Exposed locations, (4) Where 90°C derating advantage needed. Type AC is legacy - prefer MC for new commercial work.
Type NM-B Cable Ampacity (Romex) - NEC 334.80
| Cable Size | Conductors | Ampacity (60°C) | Max Breaker | Typical Use |
|---|---|---|---|---|
| 14/2 NM-B | 14 AWG Cu | 15A | 15A | Lighting, receptacles |
| 12/2 NM-B | 12 AWG Cu | 20A | 20A | General receptacles, kitchen |
| 10/2 NM-B | 10 AWG Cu | 30A | 30A | Dryer, water heater |
| 10/3 NM-B | 10 AWG Cu | 30A | 30A | Electric range, MWBC |
| 8/3 NM-B | 8 AWG Cu | 40A | 40A | Electric range (50A receptacle) |
| 6/3 NM-B | 6 AWG Cu | 55A | 55A | Subpanel feeders |
NM-B Restrictions: (1) Max 60°C rating per NEC 334.80. (2) Cannot exceed 60A per NEC 334.80. (3) Prohibited in commercial buildings >3 stories per NEC 334.10(A)(3). (4) Not permitted in exposed locations or wet areas.
Type MC Cable Ampacity (Metal-Clad) - NEC 330.80
| Cable Size | Insulation | Ampacity | Applications |
|---|---|---|---|
| 12/2 MC-THHN | 90°C (THHN) | 30A (use 25A @ 75°C term) | Commercial, exposed areas |
| 10/3 MC-THHN | 90°C (THHN) | 40A (use 35A @ 75°C term) | Feeders, industrial |
| 8/4 MC-THHN | 90°C (THHN) | 55A (use 50A @ 75°C term) | Subpanel feeders |
| 6/4 MC-THHN | 90°C (THHN) | 75A (use 65A @ 75°C term) | Large feeders, 60A circuits |
MC Cable Advantages: (1) 90°C insulation allows higher derating starting point. (2) Permitted in commercial/industrial per NEC 330.10. (3) Can exceed 60A (NM-B cannot). (4) Armor provides mechanical protection. (5) Use 75°C column for terminations per NEC 110.14(C).
Type AC Cable Ampacity (BX/Armored) - NEC 320.80
| Cable Size | Ampacity (60°C) | Max Use |
|---|---|---|
| 14/2 AC | 15A | Lighting circuits |
| 12/2 AC | 20A | General circuits |
| 10/2 AC | 30A | Limited to branch circuits |
AC Cable Limitations: Type AC (BX) typically 60°C rated, not suitable for high-ampacity feeders. Consider Type MC for commercial/industrial installations requiring >30A capacity.
For conductor ampacity without cable assembly restrictions, use NEC Ampacity Calculator. For voltage drop analysis, use Voltage Drop Calculator. For final conductor sizing, use Wire Size Calculator. Keep conduit-fill questions on the Conduit Fill Calculator; this page is for cable assemblies, not raceway occupancy.
After confirming ampacity, check that the conductor maintains voltage within acceptable limits—see the Voltage Drop Formulas Guide for NEC-based analysis.
Common Applications
Residential NM-B Cable Selection - 12/2 for 20A circuits, 10/2 for 30A dryer/water heater, 6/3 for subpanels
Commercial MC Cable Sizing - Type MC-THHN for exposed commercial installations, 90°C rating advantage
Multi-Wire Branch Circuits (MWBC) - 10/3 or 12/3 cable for split-phase 240V circuits per NEC 210.4
Kitchen/Bath Circuits - 12/2 NM-B for 20A GFCI-protected receptacles, 10/2 for dedicated appliances
Subpanel Feeders - Calculate cable size for 60A-100A subpanels using NM-B (residential) or MC (commercial)
Temperature Derating - Apply corrections for attic (hot), conduit on roof (+30°C per NEC), buried installations
Cable Bundling Analysis - Multiple cables in single raceway require ampacity adjustment per NEC 310.15(B)(3)(a)
Code Compliance Verification - Ensure cable type matches occupancy: NM-B residential only, MC for commercial
Frequently Asked Questions
Why is NM-B cable limited to 60A when the conductors can handle more current?
When using 90°C rated MC cable (THHN), why must I use 75°C ampacity for circuit sizing?
What cable should I use for Multi-Wire Branch Circuits (MWBC) and why does cable type matter?
How do I apply temperature derating to NM-B cable in hot attics and why is it more severe than MC cable?
Related Calculators
Ampacity Calculator
Individual conductor ampacity and derating per NEC 310.16 with ambient-temperature correction, current-carrying conductor adjustment, and terminal-rating limits.
ExploreWire Size Calculator
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
ExploreVoltage Drop Calculator
Calculate voltage drop in conductors
ExploreConduit Fill Calculator
Check conduit fill, conductor count, and raceway loading against NEC-style limits.
ExploreWire Gauge Converter
Convert between AWG, mm², and circular mils for conductor sizing and documentation.
ExploreCircuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
Explore