3-Phase Formulas | 480V 100A = 70.7 kW
Use 3-phase electrical formulas: 480V, 100A, PF 0.85 = 70.7 kW; 100 kW at 208V draws 327A. Compare wye/delta and kVA.
Quick Answer
What are the key three-phase formulas?
| Calculate | Formula |
|---|---|
| Power (kW) | P = √3 × V_L × I_L × PF ÷ 1000 |
| Current (A) | I = P × 1000 ÷ (√3 × V × PF) |
| Apparent Power (kVA) | S = √3 × V_L × I_L ÷ 1000 |
Where √3 = 1.732
→ Use the 3-Phase Calculator for instant calculations.
After the Formula Result
Use the formula result as the first calculation, then close the workflow with the right calculator handoff:
| If the result is... | Next check |
|---|---|
| A motor running-current estimate | Compare against the Motor Current Calculator and nameplate data |
| A service or feeder load in kVA | Review current and transformer relationships with the Transformer Calculator |
| A long circuit run | Check the same current in the Voltage Drop Calculator |
| A low power factor load | Continue with the Power Factor Calculator before sizing correction equipment |
For code-sensitive conductor, breaker, or equipment decisions, verify the adopted NEC edition, equipment listings, manufacturer instructions, and AHJ requirements before treating the formula result as final.
For a chart record, use the Single-Phase vs Three-Phase Chart when the next question is which voltage and phase model applies. Use the kVA to Amps Chart when the formula result needs line-current documentation before transformer, feeder, load-bank, or equipment review.
Three-Phase Power Formulas
Real Power (Watts/kW)
| Method | Formula | When to Use |
|---|---|---|
| Line Values | P = √3 × V_L × I_L × PF | Most common (line-to-line voltage) |
| Phase Values | P = 3 × V_ph × I_ph × PF | When phase values known |
Example: 480V, 100A, PF = 0.85
P = √3 × 480V × 100A × 0.85
P = 1.732 × 480 × 100 × 0.85
P = 70,666W = 70.7 kW
Apparent Power (VA/kVA)
| Method | Formula |
|---|---|
| Line Values | S = √3 × V_L × I_L |
| Phase Values | S = 3 × V_ph × I_ph |
Reactive Power (VAR/kVAR)
Q = √3 × V_L × I_L × sin(θ)
Q = √(S² - P²)
Line vs Phase Values
Understanding the Difference
| Term | Description | Symbol |
|---|---|---|
| Line Voltage | Voltage between any two lines (L-L) | V_L or V_LL |
| Phase Voltage | Voltage from line to neutral (L-N) | V_ph or V_LN |
| Line Current | Current in the supply line | I_L |
| Phase Current | Current through each winding | I_ph |
Star (Wye) Connection Formulas
V_L = √3 × V_ph
V_ph = V_L / √3
I_L = I_ph
Common Wye Voltages:
| Line Voltage | Phase Voltage |
|---|---|
| 208V | 120V |
| 400V | 230V |
| 480V | 277V |
| 600V | 347V |
Delta Connection Formulas
V_L = V_ph
I_L = √3 × I_ph
I_ph = I_L / √3
Star vs Delta Comparison
Voltage and Current Relationships
| Parameter | Star (Y) | Delta (Δ) |
|---|---|---|
| Line Voltage | V_L = √3 × V_ph | V_L = V_ph |
| Phase Voltage | V_ph = V_L ÷ √3 | V_ph = V_L |
| Line Current | I_L = I_ph | I_L = √3 × I_ph |
| Phase Current | I_ph = I_L | I_ph = I_L ÷ √3 |
| Power | P = √3 × V_L × I_L × PF | P = √3 × V_L × I_L × PF |
| Neutral | Available | Not available |
When to Use Each
| Configuration | Best For |
|---|---|
| Star (Wye) | Distribution systems, single-phase loads from 3-phase, motors that need reduced starting current |
| Delta | Motor running, higher starting torque, transmission (no neutral needed) |
Three-Phase Current Calculations
Current from Power (Most Common)
I = P / (√3 × V × PF)
Example: 50 kW motor, 480V, PF = 0.87
I = 50,000W / (1.732 × 480V × 0.87)
I = 50,000 / 723.5
I = 69.1A per phase
Current from kVA
I = kVA × 1000 / (√3 × V)
Example: 75 kVA transformer, 480V
I = 75,000 / (1.732 × 480)
I = 75,000 / 831.4
I = 90.2A
Current from HP (Motors)
I = HP × 746 / (√3 × V × Eff × PF)
Example: 50 HP motor, 480V, Eff = 0.92, PF = 0.87
I = 50 × 746 / (1.732 × 480 × 0.92 × 0.87)
I = 37,300 / 665.6
I = 56.0A
Three-Phase Voltage Calculations
Standard Three-Phase Voltages
| Nominal | Line-to-Line | Line-to-Neutral | Use |
|---|---|---|---|
| 208/120V | 208V | 120V | Commercial |
| 240V | 240V | 139V | Commercial Delta |
| 480/277V | 480V | 277V | Industrial |
| 600/347V | 600V | 347V | Industrial (Canada) |
Voltage Drop in Three-Phase
V_drop = √3 × I × (R × cos(θ) + X × sin(θ)) × L
For approximate calculation (copper wire):
V_drop (%) = (√3 × I × L × ρ) / (A × V) × 100
Where:
- I = Line current (A)
- L = One-way length (feet)
- ρ = Resistivity constant
- A = Wire cross-section area
→ Use Voltage Drop Calculator for accurate sizing.
Motor Full Load Current (FLC) Tables
Three-Phase Motor FLC at 460V
Based on NEC Table 430.250:
| HP | FLC (A) | HP | FLC (A) |
|---|---|---|---|
| 1 | 2.1 | 30 | 40 |
| 2 | 3.0 | 40 | 52 |
| 3 | 4.8 | 50 | 65 |
| 5 | 7.6 | 60 | 77 |
| 7.5 | 11 | 75 | 96 |
| 10 | 14 | 100 | 124 |
| 15 | 21 | 125 | 156 |
| 20 | 27 | 150 | 180 |
| 25 | 34 | 200 | 240 |
Motor FLC at Different Voltages
| HP | 208V | 230V | 460V | 575V |
|---|---|---|---|---|
| 10 | 30.8 | 28 | 14 | 11 |
| 25 | 74.8 | 68 | 34 | 27 |
| 50 | 143 | 130 | 65 | 52 |
| 100 | 273 | 248 | 124 | 99 |
→ Use Full Load Current Calculator for NEC table FLC values, or Motor Current Calculator for formula-current comparison.
Transformer Sizing
Three-Phase Transformer kVA
kVA = √3 × V × I / 1000
Or from load:
kVA = kW / PF
Standard 3-Phase Transformer Sizes
15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA
Sizing Example:
Load: 200 kW, PF = 0.85
kVA = 200 / 0.85 = 235.3 kVA
Select next size: 300 kVA transformer
Worked Examples
Example 1: Calculate 3-Phase Power
Given: 480V system, 50A per line, PF = 0.9
Solution:
P = √3 × V × I × PF
P = 1.732 × 480 × 50 × 0.9
P = 37,413W = 37.4 kW
Example 2: Current for Known Load
Given: 100 kW load, 208V, 3-phase, PF = 0.85
Solution:
I = P / (√3 × V × PF)
I = 100,000 / (1.732 × 208 × 0.85)
I = 100,000 / 306.2
I = 326.6A
Example 3: Star to Delta Conversion
Given: Star-connected motor, V_ph = 230V, I_ph = 10A
For Star:
V_L = √3 × V_ph = 1.732 × 230 = 398.4V
I_L = I_ph = 10A
If reconnected in Delta at same line voltage:
V_ph = V_L = 398.4V
I_ph = V_ph / Z = 398.4 / 23 = 17.3A (assuming same impedance)
I_L = √3 × I_ph = 1.732 × 17.3 = 30A
Power increases 3× in Delta!
Example 4: Generator Sizing
Given: Facility load 150 kW, PF = 0.8, want 25% reserve
Solution:
Required kVA = kW / PF = 150 / 0.8 = 187.5 kVA
With 25% reserve: 187.5 × 1.25 = 234.4 kVA
Select: 250 kVA generator
Unbalanced Load Calculations
Single-Phase Load on Three-Phase
For single-phase load connected line-to-neutral:
I_line = kW × 1000 / (V_ph × PF)
Balancing Three-Phase Loads
To balance loads across phases:
- Calculate total load per phase
- Move loads to equalize current
- Target within 10% imbalance
Common Mistakes to Avoid
| Mistake | Why It's Wrong | Correct Approach |
|---|---|---|
| Forgetting √3 factor | Power calculation off by 1.732 | Always use √3 for 3-phase |
| Using wrong voltage | Line vs phase confusion | Clarify V_LL or V_LN before calculating |
| Ignoring power factor | Undersized conductors | Include PF for AC loads |
| Same current Star/Delta | Currents differ by √3 | Apply correct conversion |
Related Calculators
| Calculator | Use When... |
|---|---|
| 3-Phase Power Calculator | Power and current calculations |
| Full Load Current Calculator | Motor FLC lookup |
| Motor Current Calculator | Formula-current comparison |
| Transformer Sizing | Transformer kVA selection |
| Voltage Drop Calculator | Wire sizing for distance |
Summary
Essential Three-Phase Formulas:
| Calculate | Formula |
|---|---|
| Power | P = √3 × V_L × I_L × PF |
| Current | I = P / (√3 × V × PF) |
| kVA | S = √3 × V_L × I_L |
Star vs Delta:
- Star: V_L = √3 × V_ph, I_L = I_ph
- Delta: V_L = V_ph, I_L = √3 × I_ph
Remember: √3 = 1.732
FAQ
What does √3 represent in three-phase?
√3 (1.732) is the mathematical factor that relates line and phase values due to the 120° phase shift between phases. It appears in all balanced three-phase power calculations.
How do I convert single-phase to three-phase current?
Three-phase current is lower than single-phase for the same power. Divide single-phase current by √3 (1.732) for equivalent three-phase current at the same voltage.
What is the difference between Star and Delta?
Star (Wye) has a neutral connection and different line/phase voltages (V_L = √3 × V_ph). Delta has no neutral, and line voltage equals phase voltage, but line current is √3 times phase current.
Why is 480V common for industrial?
480V three-phase offers efficient power transmission with lower currents than 208V or 240V systems. Lower current means smaller conductors and lower losses for heavy industrial loads.
How do I calculate amps from HP for a 3-phase motor?
Use I = (HP × 746) / (√3 × V × Eff × PF) or refer to NEC Table 430.250 for standard FLC values. Always use nameplate data when available.
Tags
Related Calculators
Related Guides
Ohm's Law Fundamentals for Voltage, Current, Resistance, and Power in U.S. Electrical Work
Use V = I x R and power formulas to solve simple DC and resistive AC checks, review voltage drop, and know when impedance replaces resistance in U.S. electrical troubleshooting.
Power Factor Formula | PF = kW/kVA
Use power factor formula PF = kW/kVA: 80 kW on 100 kVA gives PF 0.80; correct 100 kW from 0.70 to 0.95 with 69.1 kVAR.
Electrical Safety Fundamentals
NFPA 70E and OSHA electrical safety fundamentals for shock hazards, arc flash boundaries, PPE selection, lockout/tagout steps, and energized-work planning.
Need to Calculate Something?
Use our electrical calculators to solve your engineering problems quickly and accurately.